Datasheet: AEMC-CL601 |
 |
| AEMC Clamp-On CL601 AC Logger Description: |
 AEMC CL601 Clamp-On AC Logger is a battery powered, one channel recording device with an alkaline battery pack. This clamp-on AC logger records TRMS at a rate of up to eight times per second.
 |
| AEMC Clamp-On CL601 AC Logger Characteristics: |
| |
 0 to 600Arms Input
 |
| |
 Self contained, no exposed connections
 |
| |
 TRMS measurements
 |
| |
 Easy-to-use one button operation
 |
| |
 Overload indication
 |
| |
 Optically isolated USB 2.0 communication
 |
| Includes: |
 USB cable, DataView® CD-ROM, 2x1.5V AA-cell alkaline batteries, user manual and warranty card
 |
| Storage Modes |
 Start/Stop, FIFO and Extended Recording Mode* (XRM™)
 |
| AEMC Clamp-On CL601 AC Logger Specifications: |
| Electrical: |

 |
| Channels |
 One
 |
| Input |
 Split CT – AC Current
 |
| Measurement Range |
 0 to 600AAC
 |
| Resolution |
 0.1A
 |
| Accuracy (50/60Hz) |
 5 to 50A: ±(1% of Reading +1A)
50 to 400A: ±(1% of Reading +0.5A)
400 to 600A for duration <10min: ±(3% of Reading +1A)
 |
| Sample Rate |
 64 samples/cycle
 |
| Storage Rate |
 Programmable from 125mS to 7 days
 |
| Recording Length |
 1 minute to 8 weeks, programmable using DataView®
 |
| Memory |
 240,000 measurement (512KB)
 |
| Alarm |
 Yes
 |
| Harmonics |
 Yes - up to the 50th
 |
| Waveforms |
 Yes
 |
| Real-time Trend Viewing |
 Yes
 |
| Report Generation |
 Configurable with DataView® software
 |
| Communication |
 USB 2.0
 |
| Communication Rate |
 115200 bps
 |
| Power Source |
 2x1.5V AA-cell alkaline batteries
 |
| Battery Life |
 100 hours to >45 days
(dependent on sample rate and recording length)
 |
| Mechanical: |

 |
| Dimensions |
 9.25 x 4.0 x 1.63" (235 x 102 x 41mm)
 |
| Weight (with battery) |
 1.07 lbs (17.1 oz)
 |
| Case |
 Polycarbonate UL94-V0
 |
| Maximum Conductor Size |
 1 conductor - Ø 1.65" (42 mm)
2 conductor - Ø 1.00" (25.4 mm) each
 |
| Jaw Opening |
 1.65" (42mm) max
 |
| Vibration |
 IEC 68-2-6 (1.5mm 10 to 55Hz
 |
| Shock |
 IEC 68-2-27 (30G)
 |
| Drop |
 IEC 68-2-32 (1m)
 |
| Environmental: |

 |
| Operating Temperature |
 14° to 122°F (-10° to 50°C)
 |
| Storage Temperature |
 -4° to 140°F (-20° to 60°C)
 |
| Relative Humidity |
 0 to 85% @ 95°F (35°C), Non-condensing
 |
| Altitude |
 2000m
 |
| Safety Rating: |
 EN 61010
300V Cat. IV, 600V Cat. III
 |