Datasheet: ACD41PQ |
 |
| Amprobe ACD-41PQ Power Quality Clamp on Meter Description: |
 Amprobe ACD-41PQ Power Quality Clamp on Meter features are: TRMS sensing measures Active (W), Reactive (VAR) and Apparent (VA) Power with dual-display Power Factor readout, Total Harmonics Distortion THD, AC/DC Voltage up to 600V, AC Current up to 1000A, Resistance, Frequency, Temperature. Amprobe ACD-41PQ is a 1000A Clamp-on PQ Meter with Total Harmonics Distortion measurement.
 |
| Amprobe ACD-41PQ Power Quality Clamp on Meter Characteristics: |
| |
 Total Harmonics Distortion THD, AC/DC Voltage up to 600V, AC Current up to 1000A, Resistance, Frequency, Temperature
 |
| |
 Peak hold
 |
| |
 Optional PC interface capability (RS-232 KIT2)
 |
| |
 Audible continuity
 |
| |
 Auto power off
 |
| |
 Automatic polarity
 |
| |
 Low battery indication
 |
| |
 Data hold
 |
| |
 Large, easy to read LCD display with backlight
 |
| |
 Accommodates conductors up to 1.77” (45mm) in diameter
 |
| |
 Carrying case, test leads, batteries (installed), thermocouple and manual included
 |
| |
 Voltage overload protection for all functions up to 600V AC/DC
 |
| Amprobe ACD-41PQ Power Quality Clamp on Meter Features: |
| Instruction Manual: |
 Yes
 |
| |
 The ACD-40’s provide a simple and effective way to verify if the electrical system is affected by harmonics. Add on troubleshooting capabilities with the ACD-40PQ data logging feature or get complete Power analysis with the ACD-41PQ. Increase measuring ef
 |
| |
 THD-F is defined as: (Total Harmonic RMS / Fundamental RMS) x 100%
 |
| Replacement Parts: |
 Supplied with product
 |
| MTL-90B: |
 Set of Test Leads with Alligator Clips
 |
| TPK-59: |
 Thermocouple
 |
| SV-U: |
 CASE, UNIVERSAL
 |
| Amprobe ACD-41PQ Power Quality Clamp on Meter Specifications: |
| TRMS: |
 YES
 |
| AC Current: |
 40.0 / 400.0 / 1000 A
 |
| AC Current Basic Accuracy**: |
 +/-(1.0% Rdg + 5 LSD) @ 50 and 60Hz
 |
| DC Voltage: |
 600.0V
 |
| DC Voltage Basic Accuracy**: |
 +/-(0.5% Rdg + 5 LSD)
 |
| AC Voltage: |
 600.0V
 |
| AC Voltage Basic Accuracy**: |
 +/-(1.0% Rdg + 5 LSD) @ 50 / 60
 |
| Resistance: |
 999.9 Ohms
 |
| Resistance Basic Accuracy**: |
 +/-(1.0% Rdg + 6 LSD)
 |
| Frequency: |
 5.00Hz to 500.0Hz
 |
| Frequency Basic Accuracy**: |
 +/-(0.5% Rdg +4 LSD)
 |
| THD-F *: |
 0.0% to 99.9%
 |
| THD-F * Basic Accuracy**: |
 1.5% of Reading + 6d @ Fund Frequency
 |
| Active Power (W): |
 0 to 600.0 kW
 |
| Active Power (W) Basic Accuracy**: |
 +/-(2.0% Rdg + 6 LSD) @ Harmonics Fund to 10th & PF > 0.7
 |
| Reactive Power (VAR): |
 0 to 600.0 kVAR
 |
| Reactive Power (VAR) Basic Accuracy**: |
 +/-(2.0% Rdg + 6 LSD) @ Harmonics Fund to 10th & PF > 0.7
 |
| Apparent Power (VA): |
 0 to 600.0 kVA
 |
| Apparent Power (VA) Basic Accuracy**: |
 +/-(2.0% Rdg + 6 LSD) @ Harmonics Fund to 10th
 |
| Power Factor: |
 0.10 to 0.99
 |
| Power Factor Basic Accuracy**: |
 +/- 3 LSD @ Harmonics Fund to 21th
 |
| Temperature: |
 -58 F to 572 (-50 C to 300 C)
 |
| Temperature Basic Accuracy**: |
 +/-(2.0% Rdg + 6F) +/-(2.0 % Rdg + 3C)
 |

Need Technical Advise? Please Call: 602-795-4033