| Datasheet: |
 |
| Amprobe DGC-1000A Ground Resistance Tester Clamp-on Description: |
 Amprobe DGC-1000A Ground Resistance Tester Clamp-on performs earth fault resistance testing. Amprobe DGC-1000A features include: TRMS current measurement including leakage current test, Accurate ground resistance measurement from 0.025 to 1500ohms, etc.
 |
| Amprobe DGC-1000A Ground Resistance Tester Clamp-on Characteristics: |
| |
 Data logging capability - 116 records
 |
| |
 Individual data point recording
 |
| |
 Accurate ground resistance measurement from 0.025 to 1500W
 |
| |
 TRMS current measurement including leakage current
 |
| |
 Accurate readings regardless of power quality in less than 10 seconds
 |
| |
 Continuity beep if the resistance is lower than 40.00W
 |
| |
 Simple and easy to use, no test leads or auxiliary electrodes necessary
 |
| Amprobe DGC-1000A Ground Resistance Tester Clamp-on Features: |
| Size: |
 2.75x3.25x12.00 inch
 |
| Weight: |
 2.2 lb
 |
| Warranty: |
 Lifetime Limited Warranty
 |
| Safety: |
 CAT III 300V, CAT II 600V, CE approved
 |
| Amprobe DGC-1000A Ground Resistance Tester Clamp-on Specifications: |
| Ground resistance: |
 0.025 - 0.250, 9.999, 99.99, 199.9, 400.0, 600.0, 1500Ω ±(2% Rdg + 2 LSD)
 |
| AC Current: |
 0.200 – 1.000, 10.00, 100.0, 1000mA and 0.2 – 10.00A ±(2% Rdg + 2 LSD)
 |

Need Technical Advise? Please Call: 602-795-4033