Datasheet: Fluke-1621-KIT |
 |
| Fluke 1621 Kit Basic Earth Ground Tester Description: |
 Fluke 1621 Kit Basic Earth Ground Tester (Mfg part no Fluke 2840276) features basic ground testing methods including 3-pole Fall-of-Potential as well as 2-pole ground resistance tests. This basic earth ground tester ensures accurate measurements with automatic noise voltage detection. Kit features Includes: Fluke 1621 Tester, 2 cable reels with wire (1-50m, 1-25m)
3 earth ground stakes, 1 Test lead (red and black 2m), 2 Alligator Clips, Batteries, Users manual,
Hard carrying case.
 |
| Fluke 1621 Kit Basic Earth Ground Tester Applications: |
| |
 Electrical contractors
 |
| |
 Utility test engineers
 |
| |
 Earth ground specialists
 |
| Fluke 1621 Kit Basic Earth Ground Tester Characteristics: |
| |
 3-pole Fall-of-Potential earth testing for basic measurements
 |
| |
 2-pole resistance measurements for added versatility
 |
| |
 Easily capture values with single-button operation
 |
| |
 Ensure accurate measurements with automatic ‘noise’ voltage detection
 |
| |
 Hazardous voltage warning offers increased user protection
 |
| |
 Clearly read and record data with a large, backlit display
 |
| |
 Rugged holster and design for tough work environments
 |
| |
 Portable size allows for easy transportation
 |
| |
 Instantly be alerted to measurements outside of your set limit, when you use the adjustable limit setting
 |
| |
 600 V Cat II
 |
| Fluke 1621 Kit includes: |

 |
| |
 2 cable reels with wire (1-50m, 1-25m)
 |
| |
 3 earth ground stakes
 |
| |
 1 Test lead (red and black 2m)
 |
| |
 2 Alligator Clips
 |
| |
 Batteries
 |
| |
 Users manual
 |
| |
 Hard carrying case
 |
| Fluke 1621 Kit Basic Earth Ground Tester Specifications: |
| Measuring functions |
 3-pole earth ground resistance, 2-pole ac resistance of a conductor, Interference voltage
 |
| Intrinsic error |
 Refers to the reference temperature range and is guaranteed for one year
 |
| Measuring rate |
 2 measurements/second
 |
| Battery |
 One 9 volt alkaline (LR61)
 |
| Battery condition |
 LO-BAT is displayed if voltage drops below 6.5 V
 |
| Voltages |
 Between jacks H/C2 and E/C1: 250 Veff maximum (effective voltage)
Between jacks S/P2 and E/C1: 250 Veff maximum
 |
| Climatic class |
 VDE/VDI 3540 RZ (conforming to KWG as per DIN 40040, 4/87)
 |
| Temperature performance: |
 Working: -10 C to +50 C (+14 F to +122 F)
 |
| |
 Operating: 0 C to +35 C (+32 F to +95 F)
 |
| |
 Storage: -20 °C to +60 °C (+68 °F to +140 °F)
 |
| |
 Reference: +23 °C ± 2 °C (+73 °F ± 4 °F)
 |
| Temperature coefficient |
 Temperature coefficient 0.1 % of range per degree Kelvin
 |
| Safety |
 IEC/EN 61010-1, 600 V CAT II, pollution degree 2
 |
| Dimensions |
 113 mm x 54 mm x 216 mm (4.5 in x 2.1 in x 8.5 in), including holster
 |
| Weight |
 850 g (1.9 lb), including standard accessories, volume approximately 600 cm3
 |