Datasheet: Fluke-1750 |
 |
| Fluke 1750 Three Phase Power Recorder 2157153 Description: |
 Fluke 1750 Three Phase Power Recorder (Mfg part No. 2157153) record three-phase power quality and monitor for power quality disturbances. This three phase recorder automatically record every power quality parameter and event, on every cycle.
 |
| Fluke 1750 Three Phase Power Recorder 2157153 Applications: |
| |
 Long-term analysis
 |
| |
 Power quality surveys
 |
| |
 Quality of service compliance
 |
| |
 Semi-permanent monitoring
 |
| Fluke 1750 Three Phase Power Recorder 2157153 Characteristics: |
| Virtual Product Demo |
 Clamp Meter Demo
 |
| |
 Premium accuracy and measurement techniques: Guaranteed for all power quality parameters, with IEC 61000-4-30 Class A measurement systems
 |
| |
 Quick and reliable configuration: PDA wireless “front panel interface” provides a window into what the instrument is recording, enabling quick and reliable configuration even in awkward test locations
 |
| |
 Threshold-free set up: Apply thresholds after data is collected with Fluke Power Analyze Software
 |
| |
 Captures everything: Cross-channel and current triggering capture every measurement, on every channel, every time
 |
| |
 Intuitive PC software: Easily analyze data and generate reports
 |
| |
 Plug and play: Set up in minutes with self-identifying current probes and single-lead voltage connections
 |
| |
 No need to reconnect wires: Swap channels internally with the wireless PDA or PC when connections are not correct
 |
| |
 Measure every parameter: Voltage and current on three phases, neutral, and ground
 |
| |
 5 MHz, 8000 Vpk waveform capture: Get a detailed picture of even the shortest events
 |
| |
 Quickly retrieve data: With included SD memory card or via the 100BaseT high-speed Ethernet connection
 |
| Fluke 1750 Three Phase Power Recorder 2157153 Specifications: |
| Power quality measurement standards: |
 Conformance: IEC 61999-1-4 Class 1, IEC 61000-4-30 Class A or B depending on measurement function, IEEE519, IEEE1159, IEEE1459
 |
| |
 Clock/calendar: Leap years, 2 4-hour clock
 |
| |
 Real-time clock accuracy: Not more than ± 1 s/day
 |
| |
 Internal memory capacity for data: At least 1 GB
 |
| |
 Maximum recording period: At least 31 days
 |
| |
 Measurement time control: Automatic
 |
| |
 Maximum number of events: Limited only by the size of the internal memory
 |
| |
 Power requirements: 100 to 2 40 V rms ± 10 %, 47-63 Hz, 40 W
 |
| |
 Operating time during interruptions (internal UPS operation): 5 minutes per interruption, 60 minutes total operating time without recharging
 |
| |
 Dimensions 215 mm x 310 mm x 35 mm (8.5 in x 12.2 in x 3.5 in)
 |
| |
 Mass (weight) 6.3 kg (14 lb)
 |
| Input: |
 Measurement types: One Phase Plus Neutral, One Phase IT No Neutral, One Phase Split Phase, Three Phase Wye, Three Phase Delta, Three Phase IT, Three Phase High Leg, Three Phase Open Leg, 2 Element Delta, 21/2 Element Wye
 |
| |
 Input channels: Voltage: 4 channels, ac/dc
Current: 5 channels
 |
| |
 Voltage channels: Input resistance: 2 MΩ
Input capacitance: < 2 0 pF
 |
| |
 Current input characteristics: 2 V rms = full scale, 1 MΩ Input Impedance for ferro CTs, low impedance for Flexi-CTs
 |
| |
 Measuring method: Simultaneous digital sampling of voltage and current. Digital PLL synchronized sampling, internal frequency reference used during voltage drops.
 |
| Synchronization and sampling: |
 PLL-synchronization source: The PLL synchronizes to the A-N voltage for wye power types, and to the A-B voltage for delta power types. All listed power types can be characterized as either wye or delta.
 |
| |
 PLL lock range: 42.5 to 69 Hz
 |
| |
 Sampling frequency: Voltage and current: 2 56 samples/cycle Inter-harmonics per IEC 61000-4-7: 2 560 points/10 cycles (50 Hz), 3072 points/12 cycles (60 Hz) Transient Voltage: 5 MHz
 |
| |
 A/D resolution: Voltage and current: 2 4 bits
Transient voltage: 14 bits
 |
| Voltage and current measurements: |
 Voltage measurement range: AC voltage: 1000 V rms ± 10 % over range
DC voltage: ± 1000 V + 10 % over range
 |
| |
 Voltage crest factor: 3 or less
 |
| |
 Current measurement range: Depends on current probe used
 |
| |
 Current crest factor: 4 or less
 |
| RMS voltage: |
 Measurement type: True rms calculated continuously: every cycle, every 1/2 cycle, and every 10 or 12 cycles at 50 or 60 Hz respectively, as required by IEC 61000-4-30.
 |
| |
 Measurement uncertainty: AC: ± 0.2 % reading ± 0.1 % full scale, above 50 V rms
DC: ± 0.5 % reading ± 0.2 % full scale, above 50 V dc
 |
| RMS current: |
 Measurement type: True rms calculated continuously: every cycle, every 1/2 cycle, and every 10 or 12 cycles at 50 or 60 Hz respectively, as required by standards
 |
| Transient voltage (impulse: |
 Measurement type: Waveshape sampling
 |
| |
 Full scale: 8000 V pk
 |
| |
 Sample resolution: 200 nS
 |
| |
 Measurement uncertainty: ± 5 % reading ± 2 0 V (test parameters: 1000 V dc, 1000 V rms, 100 kHz)
 |
| Voltage swell (rms swell): |
 Measurement type: True rms (one cycle calculation by overlapping each half cycle - voltage between lines is measured for 3P3W lines and phase voltage is measured for 3P4W lines)
 |
| |
 Displayed data: Amplitude and duration of swell
 |
| |
 Measurement uncertainty: AC: ± 0.2 % reading ± 0.1 % full scale, above 50 V rms
DC: ± 0.5 % reading ± 0.2 % full scale, above 50 V dc
 |
| Voltage dip (rms sag): |
 Measurement type: True rms (one cycle calculation by overlapping each half cycle - voltage between lines is measured for 3P3W lines and phase voltage is measured for 3P4W lines)
 |
| |
 Displayed data: Amplitude and duration of dip or interruption
 |
| Voltage dropout (interruption): |
 Measurement type: True rms (one cycle calculation by overlapping each half cycle - voltage between lines is measured for 3P3W lines and phase voltage is measured for 3P4W lines)
 |
| LAN interface: |
 Connector: RJ-45
 |
| |
 Speed and type: 10/100 Base-T, auto MDIX
 |
| |
 Communications protocol: TCP/IP over Ethernet
 |
| Wireless controller interface: |
 Connection: wireless (2.4 GHz radio)
 |
| |
 Speed: up to 700 kbit/second
 |
| |
 Communications protocol: Bluetooth SPP
 |
| Power, battery life |
 Measurement type: True rms calculated continuously: every cycle, and every 10 or 12 cycles at 50 or 60 Hz respectively, as required by standards
 |
| Frequency: |
 Measurement range: 42.5 to 69 Hz
 |
| |
 Measurement source: the A-N voltage for wye power types, and to the A-B voltage for delta power types. All listed power types can be characterized as either wye or delta.
 |
| |
 Measurement accuracy: ± 10 mHz (10 to 110 % of range, with sine wave)
 |
| Power Factor: |
 Measurement range: 0.000 to 1.000
 |
| |
 Measurement accuracy: ± 1 digit from the calculation of each measured value (±3 digits for total)
 |
| Displacement power factor: |
 Measurement method: Calculated from the phase difference between voltage fundamental and current fundamental
 |
| |
 Measurement range: - 1.000 (leading) to + 1.000 (lagging)
 |
| |
 Measurement accuracy: ± 0.5 % reading ± 2 % full scale ± 1 digit
 |
| Voltage unbalance and phase sequence: |
 Measurement method: Positive sequence voltage divided by negative sequence voltage, per IEC 61000-4-30
 |
| Harmonic voltage and current: |
 Analysis window: rectangular
 |
| |
 Analysis order: 1st to 50th order
 |
| |
 Measurement accuracy: Voltage / Current: 1st to 2 0th orders: ± 0.5 % reading ± 0.2 % full scale, 2 1st to 50th orders: ± 1 % reading ± 0.3 % full scale (current sensor accuracy must be included for current and power
 |
| |
 Measurement method: IEC 61000-4-7
 |
| Inter-harmonic voltage and current (intermediate h |
 Analysis window: rectangular
 |
| |
 Analysis orders: 1.5 to 49.5th order
 |
| Environmental: |
 Operating environment: Indoors or in covered area outdoors, up to 2000 m altitude
 |
| |
 Storage temperature and humidity: -20 °C to 50 °C, 80 % RH max, non-condensing
 |
| |
 Operating temperature and humidity: 0 °C to 40 °C, 80 % RH max, non-condensing
 |
| Maximum rated working voltage: |
 Voltage terminals: 1100 V rms
 |
| |
 Voltage durability: 5550 V rms ac for 1 minute, between voltage input terminals, voltage input terminals and current probes, and voltage input terminals and case (50/60 Hz, 1 mA sense current)
 |
| |
 Enclosure protection: IP30 (per EN 60529)
 |
| Standards: |
 EMC: EN 61326-1:1997+A1:1998 Class A
EN 61000-3-2:1995+A1:1998+A2:1998
EN 61000-3-3:1995
 |
| |
 Safety: EN 61010-1 2 nd Edition; 2 000
Voltage input unit: Contamination Level 2 , Overvoltage Category 1000 V CAT III, 600 V CAT IV (anticipated overvoltage: 8000 V)
 |

Need Technical Advise? Please Call: 602-795-4033
Browse Similar Products |