Datasheet: Fluke-1760 |
 |
| Fluke 1760 Power Quality Recorder Topas 2637641 Description: |
 Fluke 1760 Power Quality Recorder Topas (Mfg part No. 2637641) is fully compliant to IEC 61000-4-30 Class-A, for advanced power quality analysis and consistent compliance testing. This power quality recorder provides the flexibility to customize thresholds, algorithms, and measurement selections.
 |
| Fluke 1760 Power Quality Recorder Topas 2637641 Applications: |
| |
 Detailed disturbance analysis
 |
| |
 Class-A quality-of-service compliance
 |
| |
 Event correlation at multiple locations
 |
| |
 Galvanic separation and DC coupling
 |
| |
 Power quality and power load studies
 |
| |

 |
| Fluke 1760 Power Quality Recorder Topas 2637641 Characteristics: |
| |
 Fully Class-A compliant
 |
| |
 GPS time synchronization
 |
| |
 Flexible and fully configurable thresholds and scale factors
 |
| |
 10 MHz, 6000 Vpk waveform capture
 |
| |
 Uninterrupted power supply (40 minutes)
 |
| |
 2 GB data memory
 |
| |
 Comprehensive software included
 |
| |
 Plug and play
 |
| |
 Rugged field design: Insulated housing and a solid state design with no rotating components
 |
| |
 In case of a power supply failure an internal battery maintains the supply for up to 40 minutes. Afterwards, or in case of discharged accumulators the Fluke 1760 is turned off and continues the measurements with the latest settings as soon as the supply voltage returns
 |
| |
 LED indicators for the status of the 8 channels, phase sequence, power supply (mains or accumulator), memory usage, time synchronization, and data transfer.
 |
| |
 2 year warranty
 |
| Fluke 1760 Power Quality Recorder Topas 2637641 Specifications: |
| Intrinsic uncertainty |
 Refers to reference conditions and is guaranteed for two years
 |
| Quality system |
 Developed, manufactured as per ISO 9001: 2000
 |
| Environment conditions: |
 Operating temp. range: 0 °C to +50 °C; 32 °F to +122 °F
 |
| |
 Working temp. range: -20 °C to +50 °C; -4 °F to +122 °F
 |
| |
 Storage temp. range: 20 °C to +60 °C; -4 °F to 140 °F
 |
| |
 Reference temperature: 23 °C ± 2 K; 74 °F ± 2 K
 |
| |
 Climatic class: B2 (IEC 654-1), -20 °C to +50 °C; -4 °F to +122 °F
 |
| |
 Max. operating altitude: 2000 m: max. 600 V CAT IV*, power supply: 300 V CAT III 5000 m: max 600 V CAT III*, power supply: 300 V CAT II
* depending on sensor
 |
| Reference conditions: |
 Environment temp.: 23 °C ± 2 K ; 74°F ± 2 K
 |
| |
 Power supply: 230 V ± 10 %
 |
| |
 Power frequency: 50 Hz / 60 Hz
 |
| |
 Signal: declared input voltage Udin
 |
| |
 Averaging: 10 minute intervals
 |
| Housing |
 Insulated, robust plastics housing
 |
| EMC: |
 Emission: Class-A as per IEC/EN 61326-1
 |
| |
 Immunity: IEC/EN 61326-1
 |
| Power supply: |
 Range: AC: 83 V to 264 V, 45 to 65 Hz
DC: 100 V to 375 V
 |
| |
 Safety: IEC/EN 61010-1 2nd edition
300 V CAT III
 |
| |
 Power consumption: max. 54VA
 |
| |
 Battery pack: NIMH, 7.2 V, 2.7 Ah
 |
| Display: |
 Power LED: • Permanent light: normal power supply from mains.
• OFF: supply via internal accumulator in case of a power failure.
 |
| |
 Channel LEDs: 3-color LEDs per channel for:
• overload condition
• under load condition
signal level in nominal range
 |
| Data memory |
 2 GB Flash memory depending on model
 |
| Memory model |
 Linear
 |
| Interfaces |
 Ethernet (100MB/s), compatible to Windows® 98/ME/NT/2000/XP RS 232, external modem via RS 232
 |
| Baud rate for RS 232 |
 9600 Baud to 115 kBaud
 |
| Dimensions |
 325 mm x 300 m x 65 mm; 2.8 x 11.8 x 2.6 in. (H x W x D)
 |
| Weight |
 Appr. 4.9 kg; 10.8 lbs.
 |
| Calibration interval |
 1 year recommended for Class-A, otherwise 2 years
 |