Main page content
The AEMC 6472 Multi-Function Ground Resistance Meter measures ground resistance (with and without clamps), bond resistance, earth coupling, touch and step potential, and soil resistivity. Measures from 0.01k? to 99.99k? with an auto-ranging feature to seek out the ideal measurement range test frequency and test current. Includes DataView software designed to analyze and display recorded measurements.
Features
| Chracteristics: | AEMC 6472 Multi-Function Ground Resistance Meter |
| Tests ground resistance with 2 clamp method | |
| Can measure ground impedance at frequencies up to 5kHz (useful for testing lightning strike protection) | |
| Capable of 3-point earth coupling measurements | |
| Features 4-point soil resistivity measurement with auto calculation of Rho and user selection of Schlumberger or Wenner test method | |
| Tests voltages 16V or 32V up to 250mA test current | |
| Automatic Shut-off feature | |
| Automatic detection of all electrode connections and their resistance values | |
| Data logs up to 512 measurements | |
| USB compatible | |
| Can be remotely operated with DataView software | |
| Ni-MH Rechargeable batteries | |
| Water and dust resistant; Case is IP54 rated when closed | |
| Includes DataView software to analyze recorded data, configure functions and parameters, and print reports | |
| Frequency range from 40 to 513Hz (automatic or manual scan) for accurate measurements | |
| 3-Pole Fall-of-potential measuring with automatic or manual frequency selection | |
| 4-Wire and 2-Wire DC resistance measurements (bond testing) with auto polarity reversal |
Specifications
| 3-Point Measurement: | |
| Range (Auto-Ranging) | 0.09? to 99.9k? |
| Resolution | 0.01? to 100? |
| Test Voltage | Nominal 16 or 32VRMS user selectable |
| Resistance Measurement Frequency | 41 to 5078Hz user selectable or automatic selection |
| Test Current | Up to 250mA |
| Accuracy | ±2% of Reading + 1ct @ 128Hz |
| Soil Resistivity 4-Point Measurement: | |
| Test Method | Wenner or Schlumberger selectable with automatic calculation of test results in ?-meters, ?-cm or ?-feet |
| Range (Auto-Ranging) | 0.01 to 99.99k?; ? Max: 999k?m (display in k?ft is not possible) |
| 4-Point Measurement Resolution | 4-Point Measurement Resolution 0.01 to 100? |
| Test Voltage | 16 or 32V user selectable |
| Frequency | From 41 to 128Hz selectable |
| External Voltage Measurement: | Range (Auto-Ranging): 0.1 to 65.0Vac/dc – DC to 440Hz Accuracy: ±2% of Reading + 1cts |
| Resistance Measurement (Bond Testing): | |
| Measurement Type | 2-Pole (with lead resistance compensation) or 4-Pole (Kelvin sensing) user selectable |
| Range (Auto-Ranging) | 2-Pole 0.01? to 99.9k?; 4-Pole 0.001? to 99.99k? |
| Accuracy | ±2% of Reading + 2cts |
| Test Voltage | 16Vdc (+, - or auto polarity) |
| Test Current | Up to 250mA max |
| Data Storage: | Memory Capacity: 512 test results Communication: Optically Isolated USB |
| Power Source | 9.6V rechargeable battery pack |
| Recharging Source | 110/220 50/60Hz external charger with 18Vdc, 1.9A output or 12V vehicle power |
Proposition 65 Warning for California Residents: This product can expose you to chemicals including Benzene, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov.
Resources