AEMC 8230 MN93-BK Precision Power Quality Analyzer Kit is a single-phase power quality analyzer that is simple to use, small, and shock-resistant. This unit is ideal for technicians and engineers for measuring and carrying out diagnostic and power quality work on single- or three-phase balanced load networks. The user will be able to obtain instant waveforms of an electrical network principal characteristics, monitoring their variation over time. AAEMC 8230 MN93-BK Precision Power Quality Analyzer Kit simultaneously handles all the measurement functions and waveform display of the various magnitudes, detection, continuous recordings and their display without any constraints. This kit includes the clamp transducer model MN93-BK.
Features
| Chracteristics: | AEMC 8230 MN93-BK Precision Power Quality Analyzer Kit |
| Up to 660Vrms or VDC measured | |
| Up to 6500AAC or 1400ADC (probe dependent) measured | |
| Min/max, Avg volts and amps, crest factor, peak and K-Factor displayed | |
| Watts, VARs and VA, power factor and displacement power factor for single-phase and balanced three-phase are calculated | |
| Total harmonic distortion (THD-F and THD-R) for voltage and current displayed | |
| Displays individual harmonic values and % for Volts and Amps through the 50th harmonic | |
| Inrush current, waveforms and statistics captured and displayed | |
| Up to eight screen captures can be stored | |
| Up to 1MB of trend recorded data can be stored | |
| DataView software or front panel configuration | |
| Stored data can be downladed to DataView software via optical with isolated USB port | |
| Up to 4096 alarm events can be captured using up to 10 different thresholds | |
| Up to 17 different power quality parameters can be displayed and recorded | |
| Includes FREE DataView software |
Specifications
| Specifications: | AEMC 8230 MN93-BK Single-Phase Power Quality Analyzer |
| Voltage (TRMS) | Phase-to-Phase: 660V Phase-to-Neutral: 600V |
| Current (TRMS) | MN Clamp: 5mA to 100mA/120A or 2 to 240A MR Clamp: 10 to 1000Aac, 10 to 1400Adc SR Clamp: 3 to 1200A AmpFlex: 10 to 6500A |
| Frequency (Hz) | 40 to 70Hz |
| Other Measurements | kW, kVAR, PF, DPF, kWh, kVARh, kVAh, K-Factor, Flicker, Harmonic Phase Shift, Phase Rotation |
| Harmonics THD-R, THD-F, V, A, VA | 1st to 50th, Direction, Sequence |
| Sampling Frequency | 256 Samples/cycle |
| Data Storage | 1.5MB partitioned for waveforms, alarms, and trend recording |
| Power Source | Six NiMH AA rechargeable battery pack AC Supply: 120/230Vac (50/60Hz) |
| Battery Life | ≥ 8 hours with display on ≥ 40 hours with display off (recording mode) |
| Electrical Specifications | |
| Mechanical Specifications | |
| Communication Port: | Optically isolated USB |
| Dimensions: | 8.3 x 4.3 x 2.4 in (211 x 108 x 60 mm) |
| Display: | 1/4 VGA (320 x 240) color LCD |
| Safety Rating: | EN 61010, 600V Cat. III, IP 54, Pollution Degree 2 |
| Weight: | 1.9 lbs (0.88kg) |
Proposition 65 Warning for California Residents: This product can expose you to chemicals including Benzene, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov.