Main page content
Fieldpiece ST4 Digital Dual-Temperature Thermometer
ST4
QVT-2012092529460686220
Environmental
HVAC
Industrial
Fieldpiece ST4 Digital Dual-Temperature Thermometer is designed to measure up to two temperatures simultaneously using Type-K thermocouples. The Fieldpiece ST4 features MIN/MAX recall functions, T1, T2, and T1-T2 measurements, data hold, and a clear easy-to-read LCD display.
Features
| Characteristics | Fieldpiece ST4 Digital Dual-Temperature Thermometer |
| Measures T1, T2, and T1-T2 | |
| Tough and durable rubber boot | |
| MIN/MAX recall functions | |
| Data freeze feature | |
| LED indicates specific probes | |
| Temperature compensation feature | |
| Switchable F/C units | |
| Includes 2 Type-K thermocouples | |
| Front case is clear and easy to view | |
| Magnetic hanger for easy hands-free measuring |
Specifications
| Specifications | Fieldpiece ST4 Dual-Temperature Meter |
| Measurement range | -58 to 2000ºF (-50 to 1300ºC) |
| Resolution | 0.1º |
| Temperature coefficient | 0.1 x (specified accuracy) per °C (0 to 18°C, 28 to 50°C) |
| System accuracy after field calibration | ±1ºF @ 30 to 120ºF with field calibration ±0.5ºC @ 0 to 50ºC with field calibration |
| Meter accuracy | Accuracies for any of the given ranges below are specified for operating temperatures between 64 to 82ºF (18 to 28ºC), for 1 year, not including thermocouple error. ±4ºF @ -58 to 32ºF ±(0.3% rdg + 2ºF) @ 32 to 1100ºF ±(0.5% rdg + 2ºF) @ 1100 to 2000ºF ±2ºC @ -50 to 0ºC ±(0.3% rdg + 1ºF) @ -50 to 600ºC ±(0.5% rdg + 1ºF) @ 600 to 1300ºC |
| Measurement rate | 2.5 readings/second |
| Battery | Single standard 9-volt battery, NEDA 1604, JIS 006P, IEC 6F22 |
| Battery life | 100 hours- carbon zinc battery. 200 hours- alkaline battery. Replace when “ “ is displayed |
| Operating enviroment | 32 to 122ºF (0 to 50°C) <70% RH |
| Storage enviroment | -8 to 140ºF (-22 to 60°C) <80% RH with battery removed from meter |
| Display | 3.5 digits LCD, 2000 count |
| Overrange | “OL” or “-OL” is displayed |
| Accessories | 9V battery (installed), 2 k-type thermocouples, 2 Velcro straps, rubber boot, case, and operator’s manual |
| Safety | Designed to meet EN61326-1, CE-EMC |
Proposition 65 Warning for California Residents: This product can expose you to chemicals including Benzene, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov.
Resources