Main page content
The Fluke 1587 T TRMS Insulation Tester and Multimeter features a true RMS digital multimeter and digital insulation tester in one compact, single unit. Offers versatility in preventative and troubleshooting maintenance.
Features
| Chracteristics: | Fluke 1587 T TRMS Insulation Tester and Multimeter |
| Insulation voltage test ranges: 1000V, 500, 250V, 100V, 50V | |
| Insulation test range: 0.01M? to 2.0G? | |
| Automatic discharge of capactive voltage feature | |
| Measures: Frequency, Capacitance, Temperature, AC/DC Voltage, DC millivolts, AC/DC milliamps | |
| Resistance range: 0.1? to 50M? | |
| Diode testing feature | |
| Continuity testing feature | |
| Includes: alligator clips, test leads, and remote probe | |
| K-type thermocouple compatible | |
| Auomatic Shut-off feature | |
| TRMS | |
| Full illiminated display | |
| Tough hard case | |
| 3 year warranty | |
| CAT III 1000V, CAT IV 600V rated | |
| Compatible with Fluke TPAK |
Specifications
| Operating temperature | –20 °C to +55 °C |
| Storage temperature | -40°C to +60°C |
| Humidity (Without Condensation) | 0% - 95% (10 °C – 30 °C) 0% - 75% (30 °C – 40 °C) 0% - 40% (40 °C – 55 °C) |
| Operating Altitude | Operating Altitude 2000 m |
| Overvoltage category | Complies with ANSI/ISA 82.02.01 (61010-1) 2004, CAN/CSA-C22.2 NO. 61010-1-04, and IEC/EN 61010-1 2nd Edition for measurement CAT III 1000 V and CAT IV 600 V |
| Agency Approvals | 2000 m CAT III 1000 V, CAT IV 600 V; 3000 m CAT II 1000 V, CAT III 600 V |
| Size | 203 x 100 x 50 mm (with holster) |
| Weight | 624 g |
| Battery life Alkaline | Meter use: 1000 hours Insulation test use: Meter can perform at least 1000 insulation tests with fresh alkaline batteries at room temperature. These are standard tests of 1000 V into 1 MΩ with a duty cycle of 5 seconds on and 25 seconds off. |
| IP Rating | IP40 |
| Voltage DC: | Maximum Voltage: 1000 V |
| Accuracy: ±(0.09%+2) | |
| Maximum Resolution: 0.001V | |
| Voltage AC: | Maximum Voltage: 1000 V |
| Accuracy: ±(2%+3) | |
| AC Bandwidth: 5kHz* *with low pass filter; 3db @ 800 Hz | |
| Maximum Resolution: 0.1 mV | |
| Current DC: | Maximum Amps: 400mA |
| Amps Accuracy: ±(0.2%+2) | |
| Maximum Resolution: 0.01 mA | |
| Current AC: | Maximum Amps: 400mA |
| Amps Accuracy: ±(1.5%+2)* *1kHz bandwidth | |
| Maximum Resolution 0.01 mA | |
| Resistance: | Maximum Resistance: 50 MΩ |
| Accuracy ±(0.9%+2) | |
| Maximum Resolution: 0.1Ω | |
| Capacitance: | Maximum Capacitance: 9,999 µF |
| Accuracy: ±(1.2%+2) | |
| Maximum Resolution: 1 nF | |
| Frequency: | Maximum Frequency: 100 kHz |
| Accuracy: ±(0.1%+1) | |
| Maximum Resolution: 0.01 Hz | |
| Temperature Measurement: | 40.0 °C to 537 °C -40.0 °F to 998 °F excluding probe |
| Diode Test: | Range: 6 V |
| Resolution: 1 mV | |
| Accuracy: ±(2% + 1) | |
| Insulation Test: | |
| Minimum Test Current @ 1kΩ/V: | 1mA |
| Maximum Resistance per Test Voltage: | 1000V: 2 GΩ |
| Maximum Resolution per Test Voltage: | 50V: 0.01 MΩ 100V: 0.01 MΩ 250V: 0.1 MΩ 500V: 0.1 MΩ 1000V: 0.1 MΩ |
| Accuracy per Test Voltage: | 50V: ±(3 % + 5) 100V: ±(3 % + 5) 250V: ±(1.5 % + 5) 500V: ±(1.5 % + 5) 1000V: ±(1.5 % + 5) to 600 MΩ, ±(10 % + 3) above 600 MΩ |
Proposition 65 Warning for California Residents: This product can expose you to chemicals including Benzene, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov.