Specifications: | TSI AirPro AP500 Air Velocity Meter with Mobile App and Optional Probes |
Model AP500 |
Barometric Pressure: | Range: 20.36 to 36.65 in. Hg / (517.1 to 930.9 mm Hg) Accuracy: ±2% of reading |
Instrument Temperature Range:
| Operating (Electronics) 40 to 113°F (5 to 45°C) |
Storage -4 to 140°F (-20 to 60°C) |
Display Interface: | Organic Light-Emitting Diode (LED) |
0.4 in. (10mm) digit height |
External Meter with Batteries: | 2.1 in. x 8.5 in. x 1.6 in. (53 mm x 181 mm x 40 mm) |
Meter Weight with Batteries: | 0.5 lbs (0.23 kg) |
Power Requirements: | AirPro Li-ion battery 3500 mAh |
AC Adapter (TSI part number 800531 only) |
Input: 90 to 240 VAC, 50 to 60 Hz |
Output: 5 VDC, 2A |
Battery: | 8+ Hours at 100 ft/min (0.5 m/s) and 77°F (25°C) |
AirPro Measurement Probes |
Key: | | V = Velocity | T = Temperature | H= Humidity | A= Articulated | S = Straight | |
Probes Available: | TH-S, VT-S, VT-A, VTH-S, VTH-A |
Velocity (VT-S, VT-A, VTH-S, VTH-A) | Range: 0 to 6,000 ft/min (0 to 30 m/s) Accuracy: ±3% of reading or ±3 ft/min (±0.015 m/s), whichever is greater Resolution: 1 ft/min (0.01 m/s) |
Temperature (VT-S, VT-A, VTH-S, VTH-A, TH-S) | Range: 14 to 150°F (-10 to 65°C) Accuracy: ±0.5°F (±0.3°C) Resolution: 0.1°F (0.1°C) |
Relative Humidity (VTH-S, VTH-A, TH-S) | Range: 5 to 95% RH Accuracy: ±3% RH Range: 0.1% RH |
Straight Probe Dimensions (VT-S, VTH-S, TH-S) | Probe length:12 in. (305 mm) Probe Diameter (largest): 0.375in. (9.5 mm) |
Articulating Probe Dimensions (VT-A, VTH-A) | Probe length: 12 in. (305 mm) Probe Diameter (largest): 0.375 in. (9.5 mm) Articulating section length: 6.0 in (15.24 cm) |
Probe Extension Dimensions (800529) | Probe Length: 12 in. (305 mm) Probe Diameter (largest): 0.375 in. (9.5 mm) |
TSI AirPro Mobile App |
Function | AirPro Feature Sets |
Basic (APFS-B) | Advanced (APFS-A) | Professional (APFS-P) |
Display Multiple Measurements Simultaneously | X | X | X |
Supports Multiple Languages | X | X | X |
Configure for Imperial or Metric Units of Measurements | | X | X |
Volumetric Flow Rate Calculation | | X | X |
Standard or Actual Velocity Calculation | X | X | X |
Max # of Instruments Connected to Airpro Mobile Simultaneously | 1 | 2 | 6 |
Wet Bulb and Dewpoint Temperature Calculation (Probe Dependent) | | X | X |
Statistics | | X | X |
Data Logging | | X | X |
Export Data | | X | X |
Enable Utilization of Instruments SD Card Slot for Data Storage | | | X |
Graphing | | | X |
Duct Traverse Application | | | X |
Online Access to Calibration Certificates | | | X |